Standard Rating Range
18 commonly offered ratings:
1016202540631001602002503154005006301000125016002500 kVA
Technical product presentation for electricity-board, EPC and private turnkey project customers.
Oil-immersed distribution transformers manufactured for utility and project requirements with CRGO cores, copper/aluminium winding options and accessories as specified.

18 commonly offered ratings:
1016202540631001602002503154005006301000125016002500 kVA
| Parameter | Typical / Offered Requirement | Reference |
|---|---|---|
| Rating | 10 kVA to 2500 kVA | Project / utility schedule |
| Voltage Class | Up to 33 kV within licensed scope | BIS licence / specification |
| Vector Group | Dyn11 for standard utility applications | As purchase specification |
| Impedance | 4% up to 250 kVA; 4.5% for 315–500 kVA; 5% for 630–2500 kVA | Catalogue framework |
| Insulation | Class A / cellulose-based system | Design / IS requirement |
| Core | CRGO | Low-loss magnetic circuit |
| Windings | Copper / Aluminium | As specified |
| Oil | Transformer oil; BDV target >60 kV after processing | IS 335 / shop process |
| Standards | IS 1180 (Part 1):2014; applicable IS 2026 requirements | BIS / purchase specification |
| Rating | No-Load Loss | Loss at 50% | Loss at 100% |
|---|---|---|---|
| 20 kVA | 145 W | 485 W | — |
| 25 kVA | 175 W | 595 W | — |
| 100 kVA | 435 W | 1500 W | — |
For tender submission, the signed BEE schedule / applicable notified table should be attached to the bid package.
GO switches configured for Haryana distribution utility requirements, including DHBVN and UHBVN applications.


Suitable for distribution-network isolation and switching applications where the utility purchase specification calls for 11 kV, 400 A GO switch assemblies.
Share your rating, voltage class, quantity, utility / project specification and delivery location — we will align the offer and documentation.